1781 Series Quad DC output Discrete
I/O Modules
(download
this web page as a pdf catalog page)
1781-OB5Q, 1781-OC5Q

1781-RO5Q, 1781-RC5Q

|
General specifications
Operating temperature range –30 to +80°C
Storage temperature range –40 to +100°C
Isolation 4,000 V rms
Capacitance input to output 8 pF
Application notes
- Do not install or remove modules in live (electrically
hot) circuits. High voltage may be present.
- Solid-state output connections are polarized.
- An externally located communicating diode must be installed
across inductive loads.
- Relay modules for resistive loads only.
- Relay output connections are not polarized.
|
Quad DC output module specifications by part number
INPUT
|
OB5Q
|
OC5Q
|
RO5Q/RC5Q1
|
| Nominal Input Voltage |
5 V dc |
5 V dc |
5 V dc |
| Minimum Input Voltage |
4 V dc |
4 V dc |
4.0 V dc |
| Maximum Input Voltage |
6 V dc |
6 V dc |
6.0 V dc |
| Drop Out Voltage |
1 V dc |
1 V dc |
1.0 V dc |
| Maximum Input Current |
15 mA dc |
15 mA dc |
27 mA dc |
| Typical Input Current |
10 mA dc |
10 mA dc |
10 mA dc |
| Nominal Input Resistance |
240 Ω |
240 Ω |
240 Ω |
| Typical V+ Current |
- |
- |
48 mA dc/channel on |
| Isolation |
4000 V rms |
4000 V rms |
1000 V rms |
OUTPUT
|
|
|
|
| Maximum Line Voltage |
60 V dc |
200 V dc |
110 V dc/125 V ac |
| Minimum Line Voltage |
3 V dc |
5 V dc |
- |
| Maximum Off-state Voltage |
60 V dc |
200 V dc |
110 V dc/125 V dc |
| Maximum Off-state Leakage |
1 mA dc |
2 mA dc |
- |
| Maximum On-state Current |
3.0* A dc |
1.0** A dc |
1A, 30 W dc ,
62.5 V A (resistive load) |
| Minimum On-state Current |
10 mA dc |
10 mA dc |
- |
| Maximum 1-second Surge |
5 A dc |
5 A dc |
2.5 A (resistive load) |
| Peak On-state Voltage @ 25°C |
1.5 V dc |
1.5 V dc |
0.25 V dc |
| Maximum Turn-on Time |
50 µ sec |
50 µ sec |
2 msec (20 cpm) |
| Maximum Turn-off Time |
100 µ sec |
100 µ sec |
1 msec (20 cpm) |
* Derate 40 mA/°C above 20°C. When operating in I/O racks that share a common
fuse between two channels, maximum on-state current must not exceed a total of
3.75 A rms @ 20° ambient for both channels.
** Derate 20 mA/°C above 60°C. When operating in I/O racks that share a common
fuse between two channels, maximum on-state current must not exceed a total of
3.75 A rms @ 20° ambient for both channels.