1781 Series Quad DC output Discrete I/O Modules

(download this web page as a .pdf* catalog page)

 

1781-OB5Q, 1781-OC5Q


1781-RO5Q, 1781-RC5Q

General specifications

Operating temperature range –30 to +80°C
Storage temperature range –40 to +100°C
Isolation 4,000 V rms
Capacitance input to output 8 pF

Application notes

  • Do not install or remove modules in live (electrically hot) circuits. High voltage may be present.
  • Solid-state output connections are polarized.
  • An externally located communicating diode must be installed across inductive loads.
  • Relay modules for resistive loads only.
  • Relay output connections are not polarized.

Quad DC output module specifications by part number

INPUT

OB5Q

OC5Q

RO5Q/RC5Q1

Nominal Input Voltage 5 V dc 5 V dc 5 V dc
Minimum Input Voltage 4 V dc 4 V dc 4.0 V dc
Maximum Input Voltage 6 V dc 6 V dc 6.0 V dc
Drop Out Voltage 1 V dc 1 V dc 1.0 V dc
Maximum Input Current 15 mA dc 15 mA dc 27 mA dc
Typical Input Current 10 mA dc 10 mA dc 10 mA dc
Nominal Input Resistance 240 Ω 240 Ω 240 Ω
Typical V+ Current - - 48 mA dc/channel on
Isolation 4000 V rms 4000 V rms 1000 V rms

OUTPUT

Maximum Line Voltage 60 V dc 200 V dc 110 V dc/125 V ac
Minimum Line Voltage 3 V dc 5 V dc -
Maximum Off-state Voltage 60 V dc 200 V dc 110 V dc/125 V dc
Maximum Off-state Leakage 1 mA dc 2 mA dc -
Maximum On-state Current 3.0* A dc 1.0** A dc 1A, 30 W dc ,
62.5 V A (resistive load)
Minimum On-state Current 10 mA dc 10 mA dc -
Maximum 1-second Surge 5 A dc 5 A dc 2.5 A (resistive load)
Peak On-state Voltage @ 25°C 1.5 V dc 1.5 V dc 0.25 V dc
Maximum Turn-on Time 50 µ sec 50 µ sec 2 msec (20 cpm)
Maximum Turn-off Time 100 µ sec 100 µ sec 1 msec (20 cpm)

*   Derate 40 mA/°C above 20°C. When operating in I/O racks that share a common
    fuse between two channels, maximum on-state current must not exceed a total of
    3.75 A rms @ 20° ambient for both channels.
** Derate 20 mA/°C above 60°C. When operating in I/O racks that share a common
    fuse between two channels, maximum on-state current must not exceed a total of
    3.75 A rms @ 20° ambient for both channels.

* Never downloaded a .pdf file before?       free software to open, read and print Portable Document Format files

 

   

   1485 Exeter Dr., Akron, OH 44306 | ph 330-733-6662 | fx 330-733-6663 | products: sales@wrcakron.com | technical support: support@wrcakron.com